Measured Data

Mass Loss Rate (MLR)

Initial-mass-normalized mass loss rate [1/s] was measured in the simultaneous thermal analyzer experiments at three heating rates: 3 K/min, 10 K/min, and 30 K/min and mass loss rate [g/s] in the cone calorimeter at three heat fluxes: 25 kW/m2, 50 kW/m2, and 75 kW/m2.

Simultaneous Thermal Analyzer

Cone Calorimeter: 25 kW/m2

Cone Calorimeter: 50 kW/m2

Cone Calorimeter: 75 kW/m2

Heat Release Rate Per Unit Area (HRRPUA)

Experiments for heat release per unit area [kW/m2] were conducted on samples conditioned at 20°C and 50% relative humidity using a cone calorimeter at three different heat fluxes: 25 kW/m2, 50 kW/m2, and 75 kW/m2.

Cone Calorimeter: 25 kW/m2

Cone Calorimeter: 50 kW/m2

Cone Calorimeter: 75 kW/m2

Carbon Monoxide (CO) Yield

Carbon monoxide yield was measured during cone calorimeter experiments conducted at heat fluxes of 25 kW/m2, 50 kW/m2, and 75 kW/m2.

Incident Heat Flux [kW/m²] Mean CO Yield [g/g] CO Yield Std. Dev. [g/g]
25 0.047 0.0
50 0.059 0.001
75 0.075 0.001

Specific Heat Release Rate

Experiments for specific heat release rate [W/g], were conducted using a micro-scale combustion calorimeter at a heating rate of 30 K/min.

Derived Data

Soot Yield

Soot yield [g/g] was calculated from smoke obscuration data collected in cone calorimeter experiments conducted at heat fluxes of 25 kW/m2, 50 kW/m2, and 75 kW/m2.

Incident Heat Flux [kW/m²] Mean Soot Yield [g/g] Soot Yield Std. Dev. [g/g]
25 0.117 0.004
50 0.106 0.002
75 0.09 0.003

Effective Heat of Combustion (Δhc)

Effective heat of combustion [MJ/kg] is calculated from data collected in both micro-scale combustion calorimeter experiments and cone calorimeter experiments.

Micro-scale Combustion Calorimeter

Value R1 R2 R3 Mean Std. Dev.
Heat of Combustion (MJ/kg) 36.6 35.59 38.11 36.77 1.04

Cone Calorimeter

Incident Heat Flux [kW/m²] Mean Effective Heat of Combustion [MJ/kg] Effective Heat of Combustion Std. Dev. [MJ/kg]
25 37.0 0.2
50 35.4 0.1
75 34.7 0.2

Band Averaged Emissivity

Band averaged emissivity was calculated from reflectance measurements conducted with an integrating sphere and Fourier transform infrared spectrometer.

Source Temperature [K] Emissivity Std. Dev.
600.0 0.954 0.001
800.0 0.941 0.001
1000.0 0.915 0.003
1200.0 0.883 0.005
1400.0 0.850 0.008
1600.0 0.819 0.011
1800.0 0.792 0.013
2000.0 0.769 0.016