Measured Data
Specific Heat
Experiments for specific heat [J/(kg K)], or heat capacity, were conducted using a heat flow meter on unconditioned and dried samples at 10 °C, 20 °C, 30 °C and 40 °C.
Unconditioned
Temperature (C) | Specific Heat Mean (J/kg-K) | Standard Deviation (J/kg-K) |
---|---|---|
10.0 | 1032.0 | 27.0 |
20.0 | 1062.0 | 25.0 |
30.0 | 1089.0 | 29.0 |
40.0 | 1099.0 | 27.0 |
Dried
Temperature (C) | Specific Heat Mean (J/kg-K) | Standard Deviation (J/kg-K) |
---|---|---|
10.0 | 794.0 | 9.0 |
20.0 | 818.0 | 18.0 |
30.0 | 834.0 | 8.0 |
40.0 | 852.0 | 18.0 |
Thermal Conductivity
Experiments for thermal conductivity [W/(m K)] were conducted using a heat flow meter on unconditioned and dried samples at 15 °C and either 45 °C or 65 °C.
Unconditioned
Temperature (C) | Conductivity Mean (W/m-K) | Standard Deviation (W/m-K) |
---|---|---|
15.0 | 0.152 | 0.006 |
45.0 | 0.153 | 0.005 |
Dried
Temperature (C) | Conductivity Mean (W/m-K) | Standard Deviation (W/m-K) |
---|---|---|
15.0 | 0.087 | 0.004 |
45.0 | 0.090 | 0.004 |
Mass Loss Rate (MLR)
Mass loss rate [kg/s] was measured in cone calorimeter experiments at three heat fluxes: 25 kW/m2, 50 kW/m2, and 75 kW/m2.
Cone Calorimeter: 75 kW/m2
Cone Calorimeter: 25 kW/m2
Cone Calorimeter: 50 kW/m2
Heat Release Rate Per Unit Area (HRRPUA)
Experiments for heat release per unit area [kW/m2] were conducted on samples conditioned at 20°C and 50% relative humidity using a cone calorimeter at three different heat fluxes: 25 kW/m2, 50 kW/m2, and 75 kW/m2.
Cone Calorimeter: 25 kW/m2
Cone Calorimeter: 50 kW/m2
Cone Calorimeter: 75 kW/m2
Carbon Monoxide (CO) Yield
Carbon monoxide yield was measured during cone calorimeter experiments conducted at heat fluxes of 25 kW/m2, 50 kW/m2, and 75 kW/m2.
Incident Heat Flux [kW/m²] | Mean CO Yield [g/g] | CO Yield Std. Dev. [g/g] |
---|---|---|
25 | 0.028 | 0.005 |
50 | 0.011 | 0.001 |
75 | 0.007 | 0.002 |
Derived Data
Effective Heat of Combustion (Δhc)
Effective heat of combustion [MJ/kg] is calculated from data collected in cone calorimeter experiments.
Cone Calorimeter
Incident Heat Flux [kW/m²] | Mean Effective Heat of Combustion [MJ/kg] | Effective Heat of Combustion Std. Dev. [MJ/kg] |
---|---|---|
25 | 1.5 | 0.6 |
50 | 6.5 | 0.4 |
75 | 7.5 | 0.5 |