Measured Data

Specific Heat

Experiments for specific heat [J/(kg K)], or heat capacity, were conducted using a heat flow meter on unconditioned and dried samples at 10 °C, 20 °C, 30 °C and 40 °C.

Unconditioned

Temperature (C) Specific Heat Mean (J/kg-K) Standard Deviation (J/kg-K)
10.0 742.0 31.0
20.0 785.0 18.0
30.0 808.0 19.0
40.0 818.0 22.0

Thermal Conductivity

Experiments for thermal conductivity [k] were conducted using a heat flow meter on unconditioned samples at 15 °C and 45 °C.

Unconditioned

Temperature (C) Conductivity Mean (W/m-K) Standard Deviation (W/m-K)
15.0 0.033 0.0
45.0 0.038 0.0

Mass Loss Rate (MLR)

Mass loss rate [kg/s] was measured in cone calorimeter experiments at three heat fluxes: 25 kW/m2, 50 kW/m2, and 75 kW/m2.

This material is not combustible. One test per heat flux level was conducted for a duration of 30 minutes. The other replicates were conducted for only 10 minutes based on the observation that no significant mass loss occurred after this time in the first replicates.

Cone Calorimeter: 25 kW/m2

Cone Calorimeter: 50 kW/m2

Cone Calorimeter: 75 kW/m2

Heat Release Rate Per Unit Area (HRRPUA)

Experiments for heat release per unit area [kW/m2] were conducted on samples conditioned at 20°C and 50% relative humidity using a cone calorimeter at three different heat fluxes: 25 kW/m2, 50 kW/m2, and 75 kW/m2.

This material is not combustible. One test per heat flux level was conducted for a duration of 30 minutes. The other replicates were conducted for only 10 minutes based on the observation that no significant mass loss occurred after this time in the first replicates.

Cone Calorimeter: 25 kW/m2

Cone Calorimeter: 50 kW/m2

Cone Calorimeter: 75 kW/m2

Carbon Monoxide (CO) Yield

Carbon monoxide yield was measured during cone calorimeter experiments conducted at heat fluxes of 25 kW/m2, 50 kW/m2, and 75 kW/m2.

This material is not combustible. One test per heat flux level was conducted for a duration of 30 minutes. The other replicates were conducted for only 10 minutes based on the observation that no significant mass loss occurred after this time in the first replicates.

Incident Heat Flux [kW/m²] Mean CO Yield [g/g] CO Yield Std. Dev. [g/g]
25 0.166 0.081
50 0.121 0.004
75 0.114 0.019

Specific Heat Release Rate

Experiments for specific heat release rate [W/g], were conducted using a micro-scale combustion calorimeter at a heating rate of 30 K/min.

Derived Data

Effective Heat of Combustion (Δhc)

Effective heat of combustion [MJ/kg] is calculated from data collected in both micro-scale combustion calorimeter experiments and cone calorimeter experiments.

Cone Calorimeter Test Notes:
This material is not combustible. One test per heat flux level was conducted for a duration of 30 minutes. The other replicates were conducted for only 10 minutes based on the observation that no significant mass loss occurred after this time in the first replicates.

Micro-scale Combustion Calorimeter

Value R1 R2 R3 Mean Std. Dev.
Heat of Combustion (MJ/kg) -47.26 -88.25 -34.85 -56.79 22.82

Cone Calorimeter

Incident Heat Flux [kW/m²] Mean Effective Heat of Combustion [MJ/kg] Effective Heat of Combustion Std. Dev. [MJ/kg]
25 -134.7 204.4
50 -49.0 73.9
75 -17.8 36.1