Measured Data

Thermal Conductivity

Experiments for thermal conductivity [W/(m K)] were conducted using a heat flow meter on unconditioned and dried samples at 15 °C and either 45 °C or 65 °C.

Unconditioned

Temperature (C) Conductivity Mean (W/m-K) Standard Deviation (W/m-K)
25.0 0.038 0.0
30.0 0.039 0.0
35.0 0.040 0.0
40.0 0.041 0.0
45.0 0.042 0.0

Mass Loss Rate (MLR)

Initial-mass-normalized mass loss rate [1/s] was measured in the simultaneous thermal analyzer experiments at three heating rates: 3 K/min, 10 K/min, and 30 K/min and mass loss rate [g/s] in the cone calorimeter at three heat fluxes: 25 kW/m2, 50 kW/m2, and 75 kW/m2.

Simultaneous Thermal Analyzer

Cone Calorimeter: 25 kW/m2

Cone Calorimeter: 50 kW/m2

Cone Calorimeter: 75 kW/m2

Heat Release Rate Per Unit Area (HRRPUA)

Experiments for heat release per unit area [kW/m2] were conducted on samples conditioned at 20°C and 50% relative humidity using a cone calorimeter at three different heat fluxes: 25 kW/m2, 50 kW/m2, and 75 kW/m2.

Cone Calorimeter: 25 kW/m2

25 kW/m² R1 25 kW/m² R2 25 kW/m² R3
Time to Sustained Ignition (s) 5.50 5.25 5.75
Time to Peak HRRPUA (s) 43.75 43.00 43.00
Peak HRRPUA (kW/m²) 479.87 444.94 450.86

Cone Calorimeter: 50 kW/m2

50 kW/m² R1 50 kW/m² R2 50 kW/m² R3
Time to Sustained Ignition (s) 1.75 1.75 1.75
Time to Peak HRRPUA (s) 30.25 29.00 29.25
Peak HRRPUA (kW/m²) 870.86 918.90 1139.19

Cone Calorimeter: 75 kW/m2

75 kW/m² R1 75 kW/m² R2 75 kW/m² R3
Time to Sustained Ignition (s) 1.50 1.50 1.00
Time to Peak HRRPUA (s) 24.50 24.25 24.25
Peak HRRPUA (kW/m²) 1185.46 1411.11 1278.14

Carbon Monoxide (CO) Yield

Carbon monoxide yield was measured during cone calorimeter experiments conducted at heat fluxes of 25 kW/m2, 50 kW/m2, and 75 kW/m2.

Incident Heat Flux [kW/m²] Mean CO Yield [g/g] CO Yield Std. Dev. [g/g]
25 0.014 0.002
50 0.011 0.0
75 0.013 0.001

Specific Heat Release Rate

Experiments for specific heat release rate [W/g], were conducted using a micro-scale combustion calorimeter at a heating rate of 30 K/min.

Derived Data

Soot Yield

Soot yield [g/g] was calculated from smoke obscuration data collected in cone calorimeter experiments conducted at heat fluxes of 25 kW/m2, 50 kW/m2, and 75 kW/m2.

Incident Heat Flux [kW/m²] Mean Soot Yield [g/g] Soot Yield Std. Dev. [g/g]
25 0.013 0.002
50 0.013 0.0
75 0.015 0.0

Effective Heat of Combustion (Δhc)

Effective heat of combustion [MJ/kg] is calculated from data collected in both micro-scale combustion calorimeter experiments and cone calorimeter experiments.

Micro-scale Combustion Calorimeter

Value R1 R2 R3 Mean Std. Dev.
Heat of Combustion (MJ/kg) 25.4 25.15 25.7 25.42 0.22

Cone Calorimeter

Incident Heat Flux [kW/m²] Mean Effective Heat of Combustion [MJ/kg] Effective Heat of Combustion Std. Dev. [MJ/kg]
25 29.8 0.2
50 28.4 2.2
75 28.9 1.2