Measured Data

Expand all

Specific Heat

Experiments for specific heat [J/(kg K)], or heat capacity, were conducted using a heat flow meter on unconditioned and dried samples at 10 °C, 20 °C, 30 °C and 40 °C.

Expand all

Unconditioned

10152025303540800100012001400160018002000
Temperature (°C)Specific Heat (J/kgK)Repository Version: 149f368
Temperature (C) Specific Heat Mean (J/kg-K) Standard Deviation (J/kg-K)
10.0 1310.0 240.0
20.0 1359.0 238.0
30.0 1433.0 267.0
40.0 1479.0 260.0

Dried

1015202530354012001250130013501400
Temperature (°C)Specific Heat (J/kgK)Repository Version: 149f368
Temperature (C) Specific Heat Mean (J/kg-K) Standard Deviation (J/kg-K)
10.0 1202.0 16.0
20.0 1260.0 24.0
30.0 1303.0 19.0
40.0 1354.0 28.0

Thermal Conductivity

Experiments for thermal conductivity [W/(m K)] were conducted using a heat flow meter on unconditioned and dried samples at 15 °C and either 45 °C or 65 °C.

Expand all

Unconditioned

20304050600.10.110.120.130.14
Temperature (°C)Thermal Conductivity (W/mK)Repository Version: 149f368
Temperature (C) Conductivity Mean (W/m-K) Standard Deviation (W/m-K)
15.0 0.114 0.008
65.0 0.126 0.009

Dried

20304050600.090.10.110.120.130.140.15
Temperature (°C)Thermal Conductivity (W/mK)Repository Version: 149f368
Temperature (C) Conductivity Mean (W/m-K) Standard Deviation (W/m-K)
15.0 0.109 0.011
65.0 0.121 0.015

Mass Loss Rate (MLR)

Simultaneous thermal analyzer experiments were conducted at three heating rates: 3 K/min, 10 K/min, and 30 K/min.

Cone calorimeter tests were conducted at a heat flux of 35 kW/m2 on samples conditioned at 20°C and 50% relative humidity.

Expand all

Simultaneous Thermal Analyzer

10020030040050060070000.0010.0020.0030.0040.005
+2σ-2σ30K/min+2σ-2σ10K/min+2σ-2σ3K/minTemperature (°C)Normalized MLR (1/s)Repository Version: 149f368

Cone Calorimeter: 35 kW/m2

010020030040050060070080000.050.10.150.20.25
R1R2R3Time (s)Mass Loss Rate (g/s)Repository Version: 149f368

Heat Release Rate Per Unit Area (HRRPUA)

Cone calorimeter tests were conducted at a heat flux of 35 kW/m2 on samples conditioned at 20°C and 50% relative humidity.

Expand all

Cone Calorimeter: 35 kW/m2

0100200300400500600700800050100150
R1R2R3Time (s)HRRPUA (kW/m​2)Repository Version: 149f368

Carbon Monoxide (CO) Yield

Cone calorimeter tests were conducted at a heat flux of 35 kW/m2 on samples conditioned at 20°C and 50% relative humidity.

Incident Heat Flux [kW/m²] Mean CO Yield [g/g] CO Yield Std. Dev. [g/g]
35 0.04 0.007

Derived Data

Expand all

Effective Heat of Combustion (Δhc)

Cone calorimeter tests were conducted at a heat flux of 35 kW/m2 on samples conditioned at 20°C and 50% relative humidity.

Expand all

Cone Calorimeter

Incident Heat Flux [kW/m²] Mean Effective Heat of Combustion [MJ/kg] Effective Heat of Combustion Std. Dev. [MJ/kg]
35 14.5 0.2