Measured Data

Mass Loss Rate (MLR)

Mass loss rate [kg/s] was measured in cone calorimeter experiments at three heat fluxes: 25 kW/m2, 50 kW/m2, and 75 kW/m2.

Cone Calorimeter: 25 kW/m2

Cone Calorimeter: 50 kW/m2

Cone Calorimeter: 75 kW/m2

Heat Release Rate Per Unit Area (HRRPUA)

Experiments for heat release per unit area [kW/m2] were conducted on samples conditioned at 20°C and 50% relative humidity using a cone calorimeter at three different heat fluxes: 25 kW/m2, 50 kW/m2, and 75 kW/m2.

Cone Calorimeter: 25 kW/m2

Cone Calorimeter: 50 kW/m2

Cone Calorimeter: 75 kW/m2

Carbon Monoxide (CO) Yield

Carbon monoxide yield was measured during cone calorimeter experiments conducted at heat fluxes of 25 kW/m2, 50 kW/m2, and 75 kW/m2.

Incident Heat Flux [kW/m²] Mean CO Yield [g/g] CO Yield Std. Dev. [g/g]
25 0.019 0.011
50 0.01 0.013
75 0.033 0.031

Derived Data

Soot Yield

Soot yield [g/g] was calculated from smoke obscuration data collected in cone calorimeter experiments conducted at heat fluxes of 25 kW/m2, 50 kW/m2, and 75 kW/m2.

Incident Heat Flux [kW/m²] Mean Soot Yield [g/g] Soot Yield Std. Dev. [g/g]
25 0.013 0.007
50 0.016 0.018
75 0.014 0.008

Effective Heat of Combustion (Δhc)

Effective heat of combustion [MJ/kg] is calculated from data collected in cone calorimeter experiments.

Cone Calorimeter

Incident Heat Flux [kW/m²] Mean Effective Heat of Combustion [MJ/kg] Effective Heat of Combustion Std. Dev. [MJ/kg]
25 12.0 6.4
50 12.6 2.1
75 11.9 1.9