Measured Data

Specific Heat

Experiments for specific heat [J/(kg K)], or heat capacity, were conducted using a heat flow meter on unconditioned and dried samples at 10 °C, 20 °C, 30 °C and 40 °C.

Unconditioned

Temperature (C) Specific Heat Mean (J/kg-K) Standard Deviation (J/kg-K)
10.0 1722.0 110.0
20.0 1759.0 141.0
30.0 1758.0 103.0
40.0 1820.0 147.0

Dried

Temperature (C) Specific Heat Mean (J/kg-K) Standard Deviation (J/kg-K)
10.0 1653.0 43.0
20.0 1665.0 42.0
30.0 1684.0 41.0
40.0 1724.0 43.0

Thermal Conductivity

Experiments for thermal conductivity [W/(m K)] were conducted using a heat flow meter on unconditioned and dried samples at 15 °C and either 45 °C or 65 °C.

Unconditioned

Temperature (C) Conductivity Mean (W/m-K) Standard Deviation (W/m-K)
15.0 0.037 0.001
65.0 0.044 0.001
45.0 NaN NaN

Dried

Temperature (C) Conductivity Mean (W/m-K) Standard Deviation (W/m-K)
15.0 0.037 0.0
65.0 NaN NaN
45.0 0.041 0.0

Mass Loss Rate (MLR)

Mass loss rate [kg/s] was measured in cone calorimeter experiments at three heat fluxes: 25 kW/m2, 50 kW/m2, and 75 kW/m2.

Cone Calorimeter: 25 kW/m2

Cone Calorimeter: 50 kW/m2

Cone Calorimeter: 75 kW/m2

Heat Release Rate Per Unit Area (HRRPUA)

Experiments for heat release per unit area [kW/m2] were conducted on samples conditioned at 20°C and 50% relative humidity using a cone calorimeter at three different heat fluxes: 25 kW/m2, 50 kW/m2, and 75 kW/m2.

Cone Calorimeter: 25 kW/m2

Cone Calorimeter: 50 kW/m2

Cone Calorimeter: 75 kW/m2

Carbon Monoxide (CO) Yield

Carbon monoxide yield was measured during cone calorimeter experiments conducted at heat fluxes of 25 kW/m2, 50 kW/m2, and 75 kW/m2.

Incident Heat Flux [kW/m²] Mean CO Yield [g/g] CO Yield Std. Dev. [g/g]
25 0.022 0.001
50 0.024 0.001
75 0.024 0.003

Specific Heat Release Rate

Experiments for specific heat release rate [W/g], were conducted using a micro-scale combustion calorimeter at a heating rate of 30 K/min.

Derived Data

Soot Yield

Soot yield [g/g] was calculated from smoke obscuration data collected in cone calorimeter experiments conducted at heat fluxes of 25 kW/m2, 50 kW/m2, and 75 kW/m2.

Incident Heat Flux [kW/m²] Mean Soot Yield [g/g] Soot Yield Std. Dev. [g/g]
25 0.023 0.002
50 0.026 0.001
75 0.026 0.001

Effective Heat of Combustion (Δhc)

Effective heat of combustion [MJ/kg] is calculated from data collected in both micro-scale combustion calorimeter experiments and cone calorimeter experiments.

Micro-scale Combustion Calorimeter

Value R1 R2 R3 Mean Std. Dev.
Heat of Combustion (MJ/kg) 26.16 25.29 25.45 25.63 0.38

Cone Calorimeter

Incident Heat Flux [kW/m²] Mean Effective Heat of Combustion [MJ/kg] Effective Heat of Combustion Std. Dev. [MJ/kg]
25 32.4 0.5
50 33.7 0.9
75 34.2 0.7

Band Averaged Emissivity

Band averaged emissivity was calculated from reflectance measurements conducted with an integrating sphere and Fourier transform infrared spectrometer.

Source Temperature [K] Emissivity Std. Dev.
600.0 0.974 0.001
800.0 0.968 0.001
1000.0 0.962 0.001
1200.0 0.957 0.002
1400.0 0.952 0.002
1600.0 0.949 0.002
1800.0 0.947 0.003
2000.0 0.944 0.003